Home » Products » Partial Discharge Measurement Device
  • Capacitance & Inductance Tester detail 1
  • Capacitance & Inductance Tester detail 2
  • Capacitance & Inductance Tester detail 3

Capacitance & Inductance TesterZC-800B

Automatic inductance capacitance tester is specially developed for problems existing in substation field measurement of capacitance value of capacitor, it solved the following problems:
① Field measurement capacitor needs dismantling cables, not only the big workload but also easy to damage the capacitor.
② Low capacitance meter output voltage causes the fault detection rate is low.
③ The instrument has characteristics of small measured workload, fast and simple, stable performance, high measurement accuracy, high fault detection, etc.
④ Reactor inductance measurement.

Features and Advantages

1. No disconnection test: The instrument is equipped with high-current high-precision current clamp. The field measurement capacitor does not need to remove the connection line, simplify the test process, effectively improve work efficiency, and avoid damage to power equipment.

2. Highly intelligent: after the completion of the three-phase test, automatically calculate the capacitance value of each phase and the total capacitance value, reactive power and other parameters, simple and intuitive, reduce the burden on testers.

3.Four-terminal measurement: using four-terminal measurement technology, accurate measurement, good test repeatability.

4.Automatic compensation: current automatic segmentation compensation, current full-scale linearization, improve instrument measurement accuracy

5.Storage function: the instrument stores a maximum of 400 data, with historical data query function

6.USB communication: USB communication function, with PC software, to achieve data analysis, save, print and generate a complete test report, easy to manage data centrally

Parameter

Capacitance measurement range and accuracyCapacitance measurement range0.1uF ~ 3300uF
Accuracy±(reading × 1% + 0.005uF)
Resolution0.001uF
Inductance measurement range and accuracyInductance measurement range100μH~50H
Accuracy±reading × 2%
Power supply and test power supplynstrument power supplyAC 220V ± 10%, 50Hz
Output voltage (open circuit)AC 23V ±10%, 50Hz (capacitance); AC 3V ±20%, 50Hz (inductance)
Maximum output current20A
Output short circuit protectionautomatic
Working conditions, dimensions and instrument weightAmbient temperature-10 °C ~ +40 °C
 relative humidity ≤90%
Host volume400 × 290 × 175mm
quality 9.5kg

Message

    WHAT CAN WE DO FOR YOU ?

    We will show you how to improve service efficiency and quality