Home » Products » Partial Discharge Measurement Device
  • ZC-800B Automatic inductance capacitance tester
  • ZC-800B Automatic inductance capacitance tester Right View
  • ZC-800B Automatic inductance capacitance tester Host
  • ZC-800B Automatic inductance capacitance tester Accessory Diagram

Automatic inductance capacitance testerZC-800A

ZC-800A Automatic inductance capacitance tester is specially developed for problems existing in substation field measurement of capacitance value of capacitor, it solved the following problems:
① Field measurement capacitor needs dismantling cables, not only the big workload but also easy to damage the capacitor.
② Low capacitance meter output voltage causes the fault detection rate is low.
The instrument has characteristics of small measured workload, fast and simple, stable performance, high measurement accuracy, high fault detection, etc.
③ Reactor inductance measurement.

Features and Advantages

1. No disconnection test: The instrument is equipped with high-current high-precision current clamp. The field measurement capacitor does not need to remove the connection line, simplify the test process, effectively improve work efficiency, and avoid damage to power equipment.

2. Highly intelligent: after the completion of the three-phase test, automatically calculate the capacitance value of each phase and the total capacitance value, reactive power and other parameters, simple and intuitive, reduce the burden on testers.

3. Four-terminal measurement: using four-terminal measurement technology, accurate measurement, good test repeatability.

4. Automatic compensation: current automatic segmentation compensation, current full-scale linearization, improve instrument measurement accuracy

5. Storage function: the instrument stores a maximum of 400 data, with historical data query function

6. USB communication: USB communication function, with PC software, to achieve data analysis, save, print and generate a complete test report, easy to manage data centrally

Parameter

Instrument measurement range and accuracy Capacitance measurement Measurable capacitance range: 0. 1μF ~ 3,300μF
Measurable capacity range: 5 ~ 20,000kvar
Measurement accuracy: ±(1.0% readings +0.02μF
Resolution: 0.001μF
Current measurement Current measurement range: 0~20A
Measurement accuracy: ±(3.0% readings +0.05A
Resolution: 0.01A
Inductance measurement Inductance measurement range:
small inductance mode 0.1mH~5mH
large inductance mode 5 mH~100H
Inductive reactance measurement range: 50mΩ~20KΩ
Measurement accuracy: ±(3.0% readings +0.05mH)
Resolution: 0.01mH
Resistance measurement Resistance measurement range:
small resistance mode 50mΩ~1Ω
large resistance mode 1Ω~20KΩ
Measurement accuracy: ±(3.0% readings +0.05Ω)
Resolution: 0.01 Ω
Working power supply Rated voltage power frequency of 220 V±10%
The rated frequency 50Hz
The rated output 1V/20V/500VA
Equipment normal working conditions Environmental temperature -10℃~+50℃
Relative humidity ≤ 90%
Display and print mode LCD display with English characters            Panel high speed printer
Shape / weight 370×260×220 mm / 12 kg

Message

    • captcha

    WHAT CAN WE DO FOR YOU ?

    We will show you how to improve service efficiency and quality