Features and Advantages
1.Low Partial Discharge Performance:
Features a specially developed epoxy-resin insulated cylinder designed to minimize internal partial discharge and ensure reliable high-voltage testing.
2.Low Impedance Voltage:
Optimized transformer design delivers low impedance voltage, providing excellent electrical performance.
3.Advanced Automatic Control:
Incorporates automatic control technology for a high level of automation, simplified operation, and strong resistance to electromagnetic interference.
4.Fast-Acting Electronic Protection:
Equipped with a rapid-response electronic protection system to enhance operational safety, equipment reliability, and long-term stability.
Parameter
- No Partial discharge transformer
- Capacitor voltage divider
- Protection resistance
- Power filter
| No Partial discharge transformer | Rated capacity | 5-1000kVA |
| Input voltage | AC220V/AC380V | |
| Output voltage | AC 0-1000kV,DC 0-1400kV | |
| Partial discharge | under rated voltage ≤5PC | |
| Impedance voltage | 10 % | |
| Output voltage waveform | power frequency, sine wave | |
| Surface temperature rise | <55℃ | |
| No-load loss | 0.2 % – 0.35 % | |
| Continuous running time allowed | 1 hour/time | |
| Intermittent running time | continuous |
| Capacitor voltage divider (double as coupling capacitor) | Gauge | 10~500KV/500PF, 1000PF |
| Rated frequency | 50HZ | |
| Nominal capacitance | 500pF, 1000pf | |
| Rated voltage | 10~500KV | |
| Nominal partial pressure ratio | 1000:1 | |
| Medium loss | < 0.2% | |
| Local discharge | < 3pC at rated voltage, < 2pC at 80% rated voltage | |
| Measuring accuracy | ≤±1% | |
| Permitted operating time | same as transformer |
| Protection resistance | Rated voltage |
| |
| Rated current | long-term current 0.1~1A | ||
| nominal resistance | 1 ~ 100 k Ω | ||
| Local discharge | < 3pC at 100% rated voltage, < 2pC at 80% rated voltage | ||
| Temperature rise | surface temperature of resistance in continuous operation under 100% rated current is less than 80K | ||
| Operating time | same as transformer |
| Power filter | Power filter | 0.38kv |
| Rated current | 150A | |
| Rated frequency | 50-60hz | |
| Number of routes | 1 | |
| quality factor of filter reactor | > 70 | |
| Background level of partial discharge | < 2pC | |
| Damping resistance power |
| |
| Attenuation characteristics | 40khz-100khz > 40DB | |
| Permissible operating time | the temperature rise of windings of the same transformer meets the national standard | |
| db Insulation level | no abnormal discharge at 5KV/1min |