Features and Advantages
1. Intelligent automatic testing for enhanced efficiency
Supports multiple modes, including automatic zinc oxide arrester testing, automatic withstand voltage testing, stepped testing, and manual testing. Based on preset parameters, the instrument automatically executes voltage ramp-up, stabilization, withstand voltage timing, and ramp-down processes, reducing manual intervention and improving testing efficiency.
2. AIPWM intelligent control technology for precise and stable measurement
Utilizes AIPWM technology to optimize the linearity of traditional PWM control, effectively enhancing control and measurement accuracy. The measurement error for both voltage and current is 1.0% ± 2 digits, with a ripple factor of no more than 1.0%, ensuring excellent output stability.
3. Wireless leakage current measurement with real-time data transmission
Equipped with a dedicated wireless microammeter, the system wirelessly transmits high-voltage side leakage current data to the main unit for real-time display. The wireless microammeter also supports smartphone connectivity via a WeChat mini-program, accommodating various operational scenarios.
4. Automatic voltage ramp rate adjustment for flexible, efficient operation
During zinc oxide arrester testing, the system automatically adjusts voltage ramp-up and ramp-down speeds based on the selected arrester voltage rating, effectively shortening test duration. It supports three speed settings—slow, medium, and fast—to meet diverse testing requirements.
5. Comprehensive safety protections ensuring test security
Features over-voltage protection, over-current protection, emergency stop, and automatic voltage reduction functions; protection thresholds for voltage and current can be customized. If test parameters exceed set limits, the instrument automatically cuts off high-voltage output and ramps the voltage down to zero, minimizing the risk of damage to the equipment and the test object.
6. Color touchscreen interface for intuitive, visual testing
Utilizes a color touchscreen interface designed for intuitive interaction, displaying test voltage, current, withstand duration, and voltage ramp curves in real-time, allowing operators to easily monitor equipment status and the testing process.
7. Data storage and report generation for streamlined test management
Supports saving test results, querying historical records, exporting data via USB, and on-site printing using a thermal printer. Dedicated PC software enables further data analysis and the generation of Word-format test reports. Built-in date and time functions facilitate record management and result traceability.
8. Support for standard communication protocols for easy data integration
Complies with the communication protocols specified in the State Grid standard Q/GDW 12482.1—2024 (“Technical Specification for Digital Test Data and Communication of Electrical Equipment”). Test data can be uploaded via an RS232 interface, meeting requirements for data transmission and integration with external systems.
9. Lightweight yet robust structure, adaptable to various testing environments
The voltage multiplier cylinder is constructed from advanced materials, offering a lightweight yet sturdy design; its exterior features specialized insulation that provides excellent electrical insulation and moisture resistance. The main unit weighs approximately 4.5 kg, while the 60 kV and 120 kV multiplier cylinders weigh about 2.6 kg and 3 kg, respectively, making them convenient to transport and use for on-site testing.
Parameter
| Specifications | 60/2 | 60/3 | 60/5 | 120/2 | 120/3 | 120/5 |
| Output Voltage (kV) | 60 | 60 | 60 | 120 | 120 | 120 |
| Output Current (mA) | 2 | 3 | 5 | 2 | 3 | 5 |
| Charging Current (mA) | 2.4 | 3.6 | 6 | 2.4 | 3.6 | 6 |
| Output Power (W) | 120 | 180 | 300 | 240 | 360 | 600 |
| Main Unit Weight (kg) | 4.5 | |||||
| Voltage Multiplier Cylinder Weight (kg) | 2.6 | 3 | ||||
| Voltage Multiplier Cylinder Dimensions (mm) | Ф100*440 | Ф100*535 | ||||
| Ripple Factor | ≤1.0% | |||||
| Voltage Measurement Error | 1.0% ± 2 digits | |||||
| Current Measurement Error | 1.0% ± 2 digits | |||||
| Overvoltage Setting Error | ≤1% | |||||
| 0.75x Voltage Setting Error | ≤1% | |||||
| Voltage Stability | ≤0.5% (with a ±10% variation in supply voltage) | |||||
| Power Supply | Single-phase AC, 50Hz, 220V ± 10% | |||||
| Operating Mode | Intermittent use: 30 minutes at rated load | |||||
| At 1.1x rated voltage: 10 minutes | ||||||
| Operating Environment | Temperature: -15°C to +50°C | |||||
| Relative Humidity: ≤90% at 25°C (non-condensing) | ||||||
| Altitude: Below 2000 meters | ||||||
| Structural Features | Fully automatic testing capability for zinc oxide surge arresters | |||||
| Manual voltage output adjustment function | ||||||