Home » News » Technical Support »
News Relevant information about Kvtester
-
What are the purposes of conducting induction withstand voltage tests on transformers?
2025-07-04For transformers, electromagnetic voltage transformers, etc., the test method of obtaining high voltage from secondary pressurization is often used to check the main insulation of the test object (referring to the insulation between windings to ground, between phases, and between windings of different voltage levels), and the insulation strength between… -
What are the precautions in the no-load test of transformers?
2025-07-01The main purpose of transformer no-load test is to measure no-load current and no-load loss, analyze their variation patterns, discover local or overall defects in the magnetic circuit, and discover winding defects. The precautions for transformer no-load test include:1. The test should be conducted at the rated tap, and the… -
What is the purpose of transformer ratio testing?
2025-07-01The transformer voltage ratio refers to the ratio of the line voltage between the primary winding and the secondary winding during no-load operation. The purpose of measuring the transformer voltage ratio is to:1. Check the correctness of the turns ratio of the transformer winding.2. Check the condition of the tap.3.… -
Factors and methods affecting the measurement results of DC high-voltage generators
2025-06-30The use of a DC high-voltage generator for DC leakage testing is a comprehensive analysis of the insulation quality of the tested product based on the magnitude of the leakage current, the changes in leakage current during continuous boosting, and the stability of leakage current during boosting. The DC withstand… -
What test items do residual magnetism have an impact on transformers?
2025-06-261. Measuring voltage ratio: Currently, when measuring voltage ratio, the voltage used is lower than the working voltage of the bridge, and the current applied to the primary winding is also relatively small. The working magnetic flux generated in the iron core is very low, and sometimes it may not… -
Precautions and solutions for transformer withstand voltage test
2025-06-26In the power system, transformers are an important type of power equipment, and their stability and reliability are crucial for ensuring the operation of the power grid. The transformer withstand voltage test is one of the important means to ensure its normal operation. However, when conducting transformer withstand voltage tests,… -
Detailed introduction of the usage method of relay protection tester
2025-06-24The relay protection tester is a key equipment for the debugging, calibration, and maintenance of power system relay protection devices. Its usage must strictly follow the operating specifications to ensure testing accuracy and equipment safety. The following are detailed usage steps and precautions:1. Preparation before use① Equipment placement and groundingPlace… -
What are the main functions of a relay protection tester?
2025-06-24The relay protection tester is a key equipment for debugging, verifying, and maintaining relay protection devices in power systems. Its main functions can be summarized as follows:1. Core functions① Fault simulation and testingFunction description: Simulate fault types such as short circuit, grounding, overload, and disconnection in power systems to verify… -
Comprehensive analysis of relay protection tester
2025-06-24Relay protection tester is a key equipment for the safe and stable operation of power systems, used to detect and verify the performance of relay protection devices. Below is an analysis from the aspects of working principle, technical parameters, application scenarios, industry standards, and development trends.1. Working principleThe relay protection… -
Precautions for using anti-interference dielectric loss tester
2025-06-20The anti-interference dielectric loss tester is an important tool used in power systems to measure the dielectric loss tangent (tg δ) and capacitance (Cx) of high-voltage electrical equipment. To ensure the accuracy of measurement results and the safety of operators, the following precautions should be taken when using:1. Safety operation…