Technical Support

What is the purpose of the transformer ratio tester test

:2025-12-08 14:19:14:

The main purpose of the transformer ratio tester is to verify the performance of the transformer, ensure the safety of the power grid, optimize operating efficiency, and comply with industry standards. Its core goal is to ensure that the equipment meets technical specifications throughout the entire life cycle of design, manufacturing, installation, and operation by accurately measuring the turns ratio and wiring group of the transformer winding. The following is a detailed explanation of the specific experimental purpose:

1. Verify transformer design parameters and manufacturing process

① Confirm the accuracy of the transformation ratio

The transformer ratio (voltage ratio between primary winding and secondary winding) is a core design parameter that directly affects the voltage conversion function. For example, the design ratio of a 10kV/0.4kV distribution transformer should be 25:1. If the actual measurement deviation exceeds the standard (such as>± 0.5%), it may be due to errors in winding turns, defects in iron core materials, or manufacturing process deviations, requiring rework or design adjustments.

② Check the correctness of the wiring group

The wiring group (such as Yyn0, Dyn11) determines the phase relationship and neutral grounding method of the transformer, which is crucial for parallel operation, relay protection, and power quality. If the group is incorrect, it may cause the phase difference of the parallel transformer to exceed the limit (>15 °), leading to circulating current and equipment burnout. The ratio tester can automatically identify groups to avoid manual wiring errors.

2. Ensure the safe and stable operation of the power grid

① Prevent equipment failures and accidents

Abnormal transformation ratio may indicate faults such as winding short circuit, poor contact of tap changer, or iron core saturation. For example, if a phase transition ratio is significantly lower than the other two phases, it may cause local overheating due to a short circuit between the windings of that phase, leading to insulation breakdown or fire. By conducting variable ratio testing, hidden dangers can be detected in advance to avoid equipment running with defects.

② Ensure compatibility in parallel operation

Transformers operating in parallel must meet the conditions of the same transformation ratio and consistent wiring group. If the transformation ratio is not consistent, it will lead to uneven load distribution, with one transformer overloaded while others are lightly loaded, accelerating equipment aging. The ratio tester can quickly verify parallel conditions and ensure system reliability.

3. Optimize the efficiency of transformer operation and power quality

① Reduce no-load losses and noise

Variable ratio deviation may cause abnormal magnetic flux in transformers under no-load conditions, increasing iron core loss (iron loss) and noise. For example, when the ratio error is greater than ± 1%, the no-load loss may increase by 5% -10%, and long-term operation will significantly increase energy consumption. By conducting a ratio test, the tap changer can be adjusted or the winding can be repaired to optimize operational efficiency.

② Improve voltage regulation capability

The on load tap changer adjusts the transformer ratio by changing the tap position to maintain stable output voltage. If the contact of the tap changer is poor or the measurement of the transformation ratio is inaccurate, it may cause voltage fluctuations to exceed the standard, affecting the normal operation of the user's equipment. The transformation ratio tester can verify whether the transformation ratio meets the expected value after the tap changer is activated, ensuring that the voltage regulation function is normal.

4. Compliant with industry standards and acceptance specifications

① Meet the testing regulations for power equipment

According to standards such as DL/T 596-2021 Preventive Testing Code for Power Equipment and GB/T 1094.5-2008 Power Transformers Part 5: Ability to withstand short circuits, transformer factory tests, handover tests, and preventive tests all require ratio testing, and error values are recorded as the basis for evaluating equipment health status.

② Through quality certification and grid connection acceptance

When power grid companies connect new substations or distributed power sources, they need to submit a transformer ratio test report as one of the grid connection conditions. If the test results are not qualified, the equipment will not be able to be put into operation, which will affect the project schedule. The automation and high-precision characteristics of the ratio tester can quickly generate reports that meet standards, accelerating the acceptance process.

5. Support fault diagnosis and status assessment

① Locate the fault location of the winding

If the imbalance of the three-phase transformation ratio exceeds the standard, it may be caused by a short circuit, disconnection or poor contact of the tap changer between turns of a certain phase winding. By comparing various phase transition ratios and historical data, the scope of the fault can be narrowed down, guiding maintenance personnel to handle it accurately.

② Assess the degree of equipment aging

Long term operation of transformers may cause winding deformation due to insulation aging, leading to changes in transformation ratio. Regular variable ratio testing can monitor equipment degradation trends, provide data support for condition based maintenance, and avoid unplanned downtime.

ZC-203AW full function variable ratio tester is based on the original requirements of user on-site use, making the operation simpler, more complete, and the data stable and reliable, greatly improving the testing speed. The equipment is suitable for various transformer ratio tests of large, medium, and small sizes. The instrument has unique functions such as unlimited scanning codes and active data uploading. The server can centrally analyze and manage data, and export data files in Excel format, greatly improving detection efficiency and saving manpower and time. It is an ideal testing instrument for the power industry.

Kvtester Electronics Technology Co.,Ltd. is a high-tech enterprise specializing in power testing, testing, research and development, production, and sales of testing equipment. It has been engaged in the electrical testing industry for many years, and its products are of high quality. We welcome customers to come and purchase. Service hotline: 0086-27-81778799, to learn more, visit the official website: www.kvtester.com


My Site © www.kvtester.com    Powered By Kvtester