Home » Products » High Voltage Test Equipment
  • Transformer Partial Discharge Induction Withstand Voltage Test System detail 1
  • Transformer Partial Discharge Induction Withstand Voltage Test System detail 2
  • Transformer Partial Discharge Induction Withstand Voltage Test System detail 5
  • Transformer Partial Discharge Induction Withstand Voltage Test System detail 4
  • Transformer Partial Discharge Induction Withstand Voltage Test System detail 3

Transformer Partial Discharge Induction Withstand Voltage Test SystemZCVF-W-150kW

The non-partial discharge variable frequency power supply can be used for AC withstand voltage test and partial discharge test of all electrical equipment. The excitation transformer is used to excite the series or parallel resonant circuit. By adjusting the output frequency of the variable frequency power supply, the inductance L of the reactor in the circuit and the capacitance C of the test object resonate. The resonant voltage is the voltage applied to the test object. Or it is directly output to the primary of the transformer through the intermediate transformer for inductive withstand voltage test.

Features and Advantages

Applicable scenarios

The non-partial discharge variable frequency power supply is the main component of the complete test system. The test system is suitable for:
1. Inductive withstand voltage and partial discharge test of power transformers.
2. AC withstand voltage and partial discharge test of mutual inductors, etc.
3. AC withstand voltage test of power cables.
4. AC withstand voltage test of GIS combined electrical appliances.
5. AC withstand voltage test of capacitive equipment such as circuit breakers, disconnectors, insulators, bushings, etc.
6. Suitable for power frequency withstand voltage test of large generator sets.
7. Suitable for power supply for large ground grid testing.

Features

1. The test has good equivalence. The output of this device is a sine wave with low waveform distortion. The waveform distortion rate is <3%, which is different from other types of variable frequency power supply devices (other types of variable frequency power supply devices are square wave outputs, which are sine waves formed by waveform shaping). Therefore, this device does not need to measure the peak value during the test.

2. It uses optical fiber control to completely isolate the high-voltage and low-voltage control circuits.

3. It is small in size, light in weight, flexible to carry, and very suitable for on-site use.

4. The operation is simple and convenient, the wiring is simple, and it can improve the work efficiency by 50% (relative to the generator set method).

5. It is safe and reliable. This device integrates a variety of protections. Including: discharge breakdown protection, overvoltage setting protection, output short circuit protection, startup zero position protection, bridge arm amplification circuit protection, power curve protection, etc. When any protection occurs, the device immediately disconnects the test voltage output and cuts off the main circuit power supply to ensure the safety of the test personnel, the test product and the test system.

6. The signal source in this device is generated by a dedicated chip and controlled by a microcomputer. The output frequency is highly stable and can reach 0.01Hz.

7. The variable frequency output voltage is controlled by TI’s high-speed microcomputer, and the output voltage instability is less than 1%.

Parameter

  • System composition
  • Main technical parameters of the system
  • Technical parameters of non-partial discharge variable frequency power supply
  • Technical parameters of non-partial discharge excitation transformer
  • Technical parameters of the reactor without partial discharge compensation
  • Technical parameters of non-partial discharge capacitor voltage divider
System composition
Name Specification Model Quantity Remarks
No PD inverter power supply WJF-150kW 1 unit
No PD excitation transformer JLB-150kVA/2×5kV; 2×15kV; 2×35kV/2×350V; 2×400V; 2×450V 1 unit
No PD compensation reactor DK-420kVA/35kV 2 units For PD test
No PD capacitor voltage divider TRF-100kV/300pF 1 unit For PD test
Main technical parameters of the system
Rated working input power 380V±10% three-phase; 50Hz
Rated output power of variable frequency power supply 150kW
Output phase number single phase
Adjustable frequency range 20Hz~400Hz, when the frequency is adjusted within the set range, the voltage is output at a constant level
Output frequency resolution 0.01Hz
Output frequency instability ≤0.1%
Output voltage waveform sine wave
waveform distortion rate ≤1.0%
System partial discharge ≤10pC
System working time The operating time during the transformer partial discharge test is 180min
 Insulation level Withstand voltage for 1min at 1.1 times the rated voltage
Technical parameters of non-partial discharge variable frequency power supply
Rated input voltage three-phase AC 380V±10%, 50Hz
Rated output power single-phase 150kW
Output frequency range 20Hz~300Hz, continuously adjustable
Rated output voltage 0~350V, continuously adjustable
Rated output current 0~428A, continuously adjustable
Frequency instability ≤0.05%
Voltage instability ≤1.0%
Nonlinear distortion ≤1%
Partial discharge ≤10pC (measured on the high-voltage side of the step-up transformer)
Working conditions temperature -10℃~+45℃, humidity: 10-90%RH, altitude: ≤1000 meters
Cooling method forced air cooling
Technical parameters of non-partial discharge excitation transformer
Rated capacity 250kVA
Low voltage winding rated voltage 2×350V; 2×400V; 2×450V
High voltage winding rated voltage 2×15kV, 2×40kV
High voltage winding rated current 2×8.3A, 2×3.1A
Working frequency 100~300Hz
Insulation level low voltage winding to ground: 3kV/1min, high voltage winding to ground: 1.1 times inductive withstand voltage/1min
Partial discharge partial discharge at rated voltage ≤10pC
Cooling method ONAN
Allowed operating time continuous operation at rated voltage and current for 90min
Technical parameters of the reactor without partial discharge compensation
Rated voltage 35kV
Rated current 12A
Inductance 9.3/5.4H (±2%)
Rated frequency range 100~300Hz
Partial discharge at rated voltage ≤10pC
Continuous working time 90min continuous working at rated current
Temperature rise winding temperature rise is less than 65K, top oil temperature rise is less than 55K
Insulation level 1.1Un/1min
Technical parameters of non-partial discharge capacitor voltage divider
Rated voltage 100kV
Working frequency 100~300Hz
Insulation level 1.1Un/1min
Total capacitance C1=500pF; C2=0.5μF. Structure: C1 is an epoxy cylinder shell oil-paper insulation structure capacitor; C2 uses the same material as C1 in temperature coefficient and frequency coefficient
System measurement error ≤±1.0%
Dielectric loss ≤0.5%
Dividing ratio 1000:1
Partial discharge amount Partial discharge amount ≤10pC at rated voltage

Message

    • captcha

    WHAT CAN WE DO FOR YOU ?

    We will show you how to improve service efficiency and quality