Home » News » Technical Support »
News Relevant information about Kvtester
-
What are the precautions for no-load testing of transformers?
2023-05-09The main purpose of transformer no-load test is to measure the no-load current and no-load loss, analyze their variation patterns, discover local or overall defects in the magnetic circuit, and discover winding defects. The precautions for transformer no-load test include:1. The test should be conducted at the rated tap, and… -
Common faults and solutions in the application of series resonance
2023-05-081. The host cannot find the resonance point.Reason: The system resonance point is outside the output frequency range of the host; System wiring error;The system is not reliably grounded; Open circuit or unreliable connection of high-voltage sampling feedback signal; The test sample has a malfunction.Exclusion method:1) Check the reliability of… -
Principle of series resonant voltage withstand test device
2023-05-081、 Principle of series resonant voltage withstand test deviceThe series resonant voltage withstand test device is a testing method that utilizes a series resonant circuit to achieve high voltage output. The basic principle is to use a transformer to raise the low voltage to the high voltage value that needs… -
The necessity of testing the voltage ampere characteristics of transformers
2023-05-06The volt ampere characteristic is the relationship between the voltage and current of the secondary winding of a current transformer. If the voltage is adjusted from small to large, and each current corresponding to the applied voltage is drawn in a coordinate system (the voltage is in the vertical coordinate… -
What are the purposes of conducting induced voltage withstand tests on transformers
2023-05-05For transformers, electromagnetic voltage transformers, etc., the main insulation of the tested object (referring to the insulation between windings to ground, between phases, and between windings of different voltage levels) is often checked by using the test method of obtaining high voltage from secondary pressurization. In addition, the insulation strength… -
What are the precautions for measuring the dielectric loss factor of transformers?
2023-04-28Measuring the dielectric loss factor is a highly sensitive test item that can detect overall moisture and deterioration of the insulation of power equipment, as well as local cracks in the small volume of tested equipment that are connected or not connected. The test precautions for measuring the dielectric loss… -
What precautions should be taken when testing the breakdown voltage of insulation oil?
2023-04-28The breakdown voltage of insulating oil is a measure of its ability to withstand voltage inside electrical equipment without being damaged, and is one of the main means to test the performance of transformer oil. The precautions for measuring the breakdown voltage of insulating oil include:1. The structural type of… -
What is the dielectric loss factor of insulating oil?
2023-04-27Under the action of the alternating electric field generated by alternating current, insulating oil theoretically only passes through a weak capacitive current inside the medium, which is 90 ° ahead of the phase of the applied voltage, only affecting the power factor of electrical equipment without generating power loss. But… -
What is the “five electrical precautions” for high-voltage switchgear?
2023-04-27The concept of five defenses1. Prevent closing the isolation switch with load.2. Prevent accidental opening and closing of circuit breakers.3. Prevent the grounding switch from closing with load.4. Prevent the load from being sent out when the grounding switch is closed.5. Prevent accidental entry into the charged area.The five prevention… -
Factors and Methods Influencing the Measurement Results of DC High Voltage Generators
2023-04-26The use of a DC high-voltage generator for DC leakage testing is a comprehensive analysis of the insulation quality of the tested product based on the magnitude of the leakage current, the changes in leakage current during continuous boosting, and the stability of the leakage current during boosting. DC withstand…